Siemens Digital Output Electronic Module from the SIMATIC ET 200S Distributed I/O System 6ES7132-4BF00-0AA0
Description
Siemens 6ES7132-4BF00-0AA0 is a digital output electronic module from the SIMATIC ET 200S distributed I/O system. It provides 8 digital outputs (DO) operating at 24 V DC, designed for controlling actuators such as solenoid valves, contactors, and indicator lamps. The module supports isochronous operation and integrates into modular ET 200S stations via compatible interface modules.
General Specifications
- Product type: Digital electronic output module
- Series: SIMATIC ET 200S
- Outputs: 8 digital outputs
- Output type: Transistor (digital)
- Width: 15 mm
- Dimensions (W × H × D): 15 × 81 × 52 mm
- Weight: ~40 g
Electrical Characteristics
- Rated load voltage (L+): 24 V DC
- Output current:
- Rated: 0.5 A per channel
- Permissible range: 7 mA to 600 mA
- Total current per module: 4 A
- Residual current (OFF state): max. 0.3 mA
- Output voltage (ON): approx. L+ minus ~1 V
- Power loss: approx. 1.5 W
- Input current (no load):
- From L+: max. 5 mA per channel
- From backplane bus: max. 10 mA
Protection and Isolation
- Short-circuit protection: Yes (per channel, ~1.5 A threshold)
- Reverse polarity protection: Yes
- Reverse voltage protection: Yes
- Electrical isolation:
- Between channels: No
- Between channels and backplane bus: Yes
- Isolation test voltage: 500 V DC
Performance Data
- Switching frequency:
- Resistive load: up to 100 Hz
- Inductive load: up to 2 Hz
- Lamp load: up to 10 Hz
- Output delay:
- OFF → ON: max. 300 µs
- ON → OFF: max. 600 µs
- Cable length:
- Unshielded: up to 600 m
- Shielded: up to 1000 m
- Load resistance range: 48 Ω to 3.4 kΩ
- Lamp load: max. 5 W
Functional Features
- Isochronous mode supported (jitter < 100 µs)
- Address space: 1 byte per module
- Parameter length: 3 bytes
- Status indication: LED per output channel (green)
- Diagnostics functions: Not supported
Application Notes
- Suitable for driving:
- Solenoid valves
- DC contactors
- Indicator lights
- Parallel switching possible for redundant control (not for increased load capacity)
- Short transient output pulse (~50 µs) may occur on power-up